7.14 Radiation Fin Temperature Rise

L4
Error Code
Method of Error
A radiation fin temperature rise is detected by checking the radiation fin thermistor with the
Detection
compressor on.
Error Decision
 If the radiation fin temperature with the compressor on is above A.
Conditions
 The error is cleared when the radiation fin temperature drops below B.
 If the error repeats, the system is shut down.
 Reset condition: Continuous run for about 60 minutes without any other error
09 class
12 class
15 class
18/24 class
Supposed
 Defective outdoor fan motor
Causes
 Short circuit
 Defective radiation fin thermistor
 Disconnection of connector
 Defective outdoor unit PCB
 Silicone grease not applied properly on the radiation fin after replacing the outdoor unit PCB
Part 6 Service Diagnosis
A
B
(°C)
(°F)
(°C)
99
210.2
70
90
194
84
183.2
100
212
57
134.6
82
179.6
77
170.6