Radiation Fin Temperature Rise - Daikin 2MXS-W Series Service Manual

Multi-split type air conditioners
Table of Contents

Advertisement

SiUS122226E

7.19 Radiation Fin Temperature Rise

L4
Error Code
Outdoor Unit LED
A j 1 h 2 h 3 h 4 i 5 h
Display
Method of Error
A radiation fin temperature rise is detected by checking the radiation fin temperature with the
Detection
compressor on.
Error Decision
 The radiation fin temperature with the compressor on is above A.
Conditions
 The error is cleared when the temperature drops below B.
 If the error repeats, the system is shut down.
 Reset condition: Continuous run for about 60 minutes without any other error
A
B
Supposed
 Defective outdoor fan motor
Causes
 Short circuit
 Defective radiation fin thermistor
 Disconnection of connector
 Defective outdoor unit PCB
 Silicone grease not applied properly on the radiation fin after replacing the outdoor unit PCB
Part 6 Service Diagnosis
2/3/4MXS
5MXS
°C
°F
°C
90
194
70
85
185
64
Troubleshooting for Outdoor Unit
2/3MXL(H)
°F
°C
°F
158
90
194
147.2
85
185
4MXL(H)
°C
°F
70
158
64
147.2
219