7.19 Radiation Fin Temperature Rise
L4
Error Code
Outdoor Unit LED
A j 1 h 2 h 3 h 4 i 5 h
Display
Method of Error
A radiation fin temperature rise is detected by checking the radiation fin temperature with the
Detection
compressor on.
Error Decision
The radiation fin temperature with the compressor on is above A.
Conditions
The error is cleared when the temperature drops below B.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
A
B
Supposed
Defective outdoor fan motor
Causes
Short circuit
Defective radiation fin thermistor
Disconnection of connector
Defective outdoor unit PCB
Silicone grease not applied properly on the radiation fin after replacing the outdoor unit PCB