7.17 Radiation Fin Temperature Rise
L4
Error Code
Method of Error
A radiation fin temperature rise is detected by checking the radiation fin thermistor with the
Detection
compressor on.
Error Decision
If the radiation fin temperature with the compressor on is above A.
Conditions
The error is cleared when the radiation fin temperature drops below B.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
09/12 class
15/18/24 class
Supposed
Defective outdoor fan motor
Short circuit
Causes
Defective radiation fin thermistor
Disconnection of connector
Defective outdoor unit PCB
Silicone grease not applied properly on the radiation fin after replacing the outdoor unit PCB
Part 6 Service Diagnosis
A
B
°C
°F
°C
99
210.2
70
100
212
57
Troubleshooting for Outdoor Unit
°F
158
134.6
185