UPS MAINTENANCE

How to Replace UPS Internal Batteries

The UPS internal batteries are heavy (see page 114). Each battery tray holds two rows of five
batteries. Use caution when handling the heavy battery trays.
To replace the battery trays in the UPS cabinet:
1.
2.
NOTE Disconnecting the control panel from the electronics module automatically transfers
the UPS to Bypass mode.
104
EATON Powerware
Verify that the battery circuit breaker is in the OFF (O) position (see
Figure 32 on page 49).
Remove the UPS front cover and set it aside (see Figure 52):
Grasp the fingergrips on both sides of the cover and pull the cover
forward firmly. Unplug the LCD cable connecting the back of the
control panel to the electronics module.
LCD Cable
Figure 52. Removing the UPS Front Cover
®
BladeUPS
®
(12 kVA) User's Guide
C A U T I O N
S
164201649 Rev 3 www.powerware.com