SPECIFICATIONS
Table 13. Electrical Output
Nominal Output Voltage
Output Voltage Variation
(Standard)
Output Voltage Variation
(Reduced)
Output Receptacles
Short Circuit Capability
(Battery Mode)
Short Circuit Capability
(Normal Mode)
Nominal Output Frequency
Output Frequency Variation
Output Overload
Voltage Waveform
Full Output
116
EATON Powerware
BladeUPS 12
120/208 Vac three-phase
104–132 Vac phase to neutral,
180–229 Vac phase to phase
108–132 Vac phase to neutral,
187–229 Vac phase to phase
Anderson connector
84A, <300 ms
Limited by 50A input breaker
50–60 Hz auto-detection (Normal mode)
50 or 60 Hz (Battery mode)
Synchronized (Normal mode)
±0.1 when not synchronized with source (Battery mode)
100–110%: load transfers to Bypass mode after 10 minutes
110–125%: load transfers to Bypass mode after 1 minute
125–150%: load transfers to Bypass mode after 5 seconds
>150%: load transfers to Bypass mode after 300 ms
Normal mode and Battery mode: Sine wave; <2% THD with linear load;
®
BladeUPS
®
(12 kVA) User's Guide
BladeUPS 12i
230/400 Vac three-phase
207–253 Vac phase to neutral,
358–438 Vac phase to phase
Not applicable
Anderson connector
44A, <300 ms
Limited by 30A input breaker
<5% with nonlinear load
Three-phase
S
164201649 Rev 3 www.powerware.com