Eaton Powerware BladeUPS User Manual page 35

12 kva
Hide thumbs Also See for Powerware BladeUPS:
Table of Contents

Advertisement

8.
Ground
Top Entry
Terminal Block
Table 2. BladeUPS Bar Wiring Specifications
BladeUPS Bar
Terminal
Terminal Block
Output
1 [Output A]
2 [Output B]
3 [Output C]
Input
4 [Input A]
5 [Input B]
6 [Input C]
Neutral
Safety Ground
2
* Use 13.3 mm
(6 AWG) 90_C copper wire minimum.
EATON Powerware
Connect the input, output, and ground wires to the BladeUPS Bar
terminal block according to Figure 8 and Table 2. Route the three
input phases and the input neutral through the mounted or
loosened ferrite assembly (see Figure 5 or Figure 7).
Ground
Figure 8. BladeUPS Bar Terminal Block
BladeUPS Bar
Position
Wire Function
Phase 1 Out
Phase 2 Out
Phase 3 Out
Phase 1 In
Phase 2 In
Phase 3 In
7
Neutral
8
Neutral
9
Neutral
Ground
Ground
®
BladeUPS
®
(12 kVA) User's Guide
Terminal Wire
Size Rating*
2
13.3 mm
(6 AWG) to
2
177 mm
(350 kcmil)
NOTE Wire gauge
depends on
overcurrent
protection rating
required (see Table 1
on page 21).
Reference the NEC,
NFPA 70, for wire
sizing.
2
18 mm
(4 AWG) to
2
215 mm
(400 kcmil)
S
164201649 Rev 3 www.powerware.com
INSTALLATION
Bottom Entry
Terminal Block
Tightening
Torque
31.1 Nm (275 lb in)
1.8 Nm (16 lb in)