Ups Maintenance; Ups And Battery Care; Storing The Ups And Batteries - Eaton Powerware BladeUPS User Manual

12 kva
Hide thumbs Also See for Powerware BladeUPS:
Table of Contents

Advertisement

Chapter 6

UPS and Battery Care

Storing the UPS and Batteries

EATON Powerware

UPS Maintenance

This section explains how to
S
Care for the UPS and batteries
S
Replace the UPS batteries and EBMs
S
Test new batteries
S
Replace the electronics module
S
Recycle used batteries or UPS
S
Update the UPS firmware
For the best preventive maintenance, keep the area around the UPS
clean and dust‐free. If the atmosphere is very dusty, clean the outside of
the system with a vacuum cleaner.
For full battery life, keep the UPS at an ambient temperature of
25°C (77°F).
NOTE The batteries in the UPS are rated for a 3–5 year service life. The length of service
life varies, depending on the frequency of usage and ambient temperature. Batteries used
beyond expected service life will often have severely reduced runtimes. Replace batteries at
least every 5 years to keep units running at peak efficiency.
If you store the UPS for a long period, recharge the battery every
6 months by connecting the UPS to utility power. The batteries charge
to 80% capacity in less than 5 hours. However, it is recommended that
the batteries charge for 48 hours after long-term storage.
Check the battery recharge date on the shipping carton label. If the date
has expired and the batteries were never recharged, do not use the
UPS. Contact your service representative.
®
®
BladeUPS
(12 kVA) User's Guide
S
164201649 Rev 3 www.powerware.com
101