Communication Options - Eaton Powerware BladeUPS User Manual

12 kva
Hide thumbs Also See for Powerware BladeUPS:
Table of Contents

Advertisement

Communication Options

The BladeUPS has serial communication capabilities through the DB-9
communication port or through an X-Slot card in one of the available
bays.
The UPS supports two serial communication devices according to the
following table:
Independent
X-Slot 1
Any X-Slot card
Any X-Slot card
Any X-Slot card
NOTE You can configure relays, signal inputs, and the serial port baud rate through the
front panel menus (see Table 4 on page 74).
NOTE In a UPS connected to utility power, X-Slot cards remain powered on even if the
input breaker is off.
EATON Powerware
X-Slot 2
Any X-Slot card except the
Powerware Modem Card
Powerware Relay Interface Card
Powerware Hot Sync CAN Bridge Card
Not in use
®
BladeUPS
®
(12 kVA) User's Guide
Multiplexed
DB-9 Communication Port
Not in use
Available
Available
S
164201649 Rev 3 www.powerware.com
COMMUNICATION
91

Advertisement

Table of Contents
loading

Table of Contents