OPERATION
6.
7.
8.
9.
10. Press any button on the front panel display to activate the menu
11. Switch the load connector circuit breaker to the ON (
12. Press the
82
EATON Powerware
Check the UPS front panel display for active alarms or notices
(other than "Batteries Disconnected"). Resolve any active alarms
before continuing. See "Troubleshooting" on page 119.
Switch the UPS battery circuit breaker to the ON (
If optional EBMs are installed, switch all EBM battery circuit
|
breakers to the ON (
) position.
Verify that the "Batteries Disconnected" alarm has cleared. Verify
that no other alarms appear on the UPS front panel display.
If the
indicator is flashing, do not proceed until all alarms are
clear. Check the UPS status from the front panel to view the active
alarms. Correct the alarms and restart if necessary.
options. Select CONTROL and GO TO BYPASS MODE.
The
indicator illuminates solid and the
indicating the UPS is operating in Bypass mode. The load is now
powered by utility power.
If the
indicator is flashing, do not proceed until all alarms are
clear. Check the UPS status from the front panel to view the active
alarms. Correct the alarms and restart if necessary.
button until the Eaton Powerware logo appears.
ESC
®
BladeUPS
®
(12 kVA) User's Guide
indicator flashes,
S
164201649 Rev 3 www.powerware.com
|
) position.
|