Remote Emergency Power-Off - Eaton Powerware BladeUPS User Manual

12 kva
Hide thumbs Also See for Powerware BladeUPS:
Table of Contents

Advertisement

Remote Emergency Power-off

REPO is used to shut down the UPS from a distance. This feature can
be used for shutting down the load and the UPS by thermal relay, for
instance in the event of room overtemperature. When REPO is
activated, the UPS shuts down all converters, de-energizes all system
relays, trips the UPS battery circuit breaker, and fully powers down
within 10-15 seconds.
The REPO circuit is an IEC 60950 safety extra low voltage (SELV) circuit. This circuit must be
separated from any hazardous voltage circuits by reinforced insulation.
S
The REPO must not be connected to any utility connected circuits. Reinforced insulation
to the utility is required. The REPO switch must have a minimum rating of 24 Vdc and
20 mA and be a dedicated latching-type switch not tied into any other circuit. The REPO
signal must remain active for at least 250 ms for proper operation.
S
To ensure the UPS stops supplying power to the load during any mode of operation, the
input power must be disconnected from the UPS when the emergency power-off function
is activated.
NOTE For Europe, the emergency switch requirements are detailed in Harmonized
document HD-384-48 S1, "Electrical Installation of the Buildings, Part 4: Protection for
Safety, Chapter 46: Isolation and Switching."
Wire Function
REPO
L1
L2
NOTE Leave the REPO connector installed in the REPO port on the UPS even if the REPO
function is not needed.
There are two REPO positions that may be used, normally-open (NO) or
normally-closed (NC). See Figure 47 on page 89 for REPO locations.
EATON Powerware
®
BladeUPS
®
(12 kVA) User's Guide
W A R N I N G
C A U T I O N
REPO Connections
Terminal Wire Size Rating
2
4–0.32 mm
(12–22 AWG)
S
164201649 Rev 3 www.powerware.com
COMMUNICATION
Suggested Wire Size
2
0.82 mm
(18 AWG)
95