OPERATION

User Settings

The following table displays the options that can be changed by the
user.
Table 4. User Settings
Description
Set Date and Time
Display Contrast
Change Language
Relay Config
Signal Inputs
Serial Port Config
Parallel Operation Settings
74
EATON Powerware
Available Settings
Set Year, Month, Day
Date: mm/dd/yyyy
Set Hours, Minutes
Time is a 24-hour clock.
Adjust contrast with up/down arrow buttons
Select Language
Available languages depend on model and
languages installed.
Relay: [Alarm-1] [X-Slot 1-1/2/3/4] or
[X-Slot 2-1/2/3/4]
Setup: [On Battery] [Summary Alarm]
[On Bypass] [UPS OK] [custom] [empty]
Signal: [X-Slot-1] [X-Slot-2] [INPUT 1]
[INPUT 2]
[signal inputs]
Logic: [0] [1]
For more information, see "Programmable
Signal Inputs" on page 97.
Port: [X-Slot-1] [X-Slot-2/Serv]
Speed: [19200] [9600] [2400] [1200]
System Display Subunit: [Unit #1...6]
Selects which unit the System display
communicates with.
Parallel Operation Mode:
[Redundant Mode] [Capacity Mode]
This setting is not available for six-unit systems
(must be Redundant Mode only).
Parallel XCP: [System] [Sub Unit]
Select Sub Unit for PowerVision software.
Select System for other software.
®
BladeUPS
®
(12 kVA) User's Guide
Default Setting
01/01/2003
00:00
Moderate
English
Alarm 1: empty
X-Slots (1 or 2)
#1: UPS OK
#2: On Bypass
#3: Summary Alarm
#4: On Battery
<empty>
[1]
19200
Unit #1
Redundant Mode
System
S
164201649 Rev 3 www.powerware.com