Mitsubishi Electric MELSEC Q Series User Manual page 103

Programmable controller multiple cpu system
Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

(2) Modules that have restrictions on use of a Built-in Ethernet port QCPU
Table2.24 lists the module that have restrictions on use of a Built-in Ethernet port QCPU.
MELSECNET/H module
Serial communication module
Modem interface module
Web server module
MES interface module
*1: If the MELSECNET module meets the following all conditions, use the MELSECNET/H module whose serial number (first
five digits) is "10042" or later.
1.A multiple CPU system containing a Built-in Ethernet port QCPU is configured.
2.To an Ethernet port of a Built-in Ethernet port QCPU, GX Developer or GOT is connected.
3.From GX Developer or GOT, access is made to another station through a MELSECNET/H module controlled by another
CPU.
4.The access target on another station is an A/QnA series CPU module.
(3) Combination of power supply module, base unit and QCPU
Combination of power supply module, base unit and QCPU has some restrictions.
For details, refer to the following:
QCPU User's Manual (Hardware Design, Maintenance and Inspection)
(Example) The redundant power supply module can be mounted only on the redundant power main base unit
or the redundant power extension base unit.
2 - 55
Table2.24 Modules that have restrictions on use of a Built-in Ethernet port QCPU
Product name
Model
QJ71LP21-25
QJ71LP21S-25
QJ71LP21G
QJ71BR11
QJ71C24N
QJ71C24N-R2
QJ71C24N-R4
QJ71CMON
QJ71WS96
QJ71MES96
Five digits of available
serial No.
Some modules have restrictions
depending on the use conditions.
10042 or later
10012 or later

Advertisement