15-30kVA Specifications – w/ Internal Battery Backup
4400 SPECIFICATIONS: 15–30kVA w/ Internal Battery Backup
Specification
General
Model Number
(B – Internal Batt. Backup)
Capacity Output
Topology
Input
Voltage (V)
No. Internal Transformers (Max)
Current (Nominal) (A)
Current (Max) (A)
Current Limit (%)
Current THD (%)
Frequency (Hz)
Input Power Factor (PF) @ full
load
Walk-in Function (sec)
Cold Start (0-100% load) (sec)
Bypass
Voltage (V)
Frequency (Hz)
Bypass Overload @ 125% Load
Bypass Overload @ 150% Load
Bypass Overload @ 1000%
Load
Automatic Retransfer (Max load
% for Retansfer)
Output
Voltage (V)
Voltage Regulation (%)
Voltage Total Harmonic Distor-
tion (Full Linear Load) (%)
Output Voltage Adjustment (%)
Voltage Transient Response
(%) @ 100% Step Load
Change
1 - Requires adjustment of factory/service adjustable parameters.
50
15kVA
20kVA
4400F3F150XAB
4400F3F200XAB
15 kVA (13.5kW)
20 kVA (18kW)
Double conversion all-IGBT UPS
208/120 V +10% to -15% (Intermittently to -30% at 70% load
0 (No Internal Transformers)
42 A
55 A
46 A
60 A
125% of Rated Load Current
20% to 100% over 5 sec.
25 sec. from cold start
208/120 V, 3P/4W +GND
10 min. @ 125% Load
1 cycle @ 1000% Load
208/120 V, 3P/4W +GND
± 2% at 0-100% Balanced Load
± 5% via Touchscreen
± 3% @ 100% Step Load Change
4400 Series Installation and Operation Manual – 64527-006
25kVA
4400F3F250XAB
25 kVA (22.5kW)
69 A
74 A
< 5%
50/60 Hz ± 5 Hz
>0.98
(not selectable)
50/60 Hz ±5%
2 min. @ 150% Load
Yes
< 3%
30kVA
4400F3F300XAB
30 kVA (27kW)
) 3P/4W +GND
1
83 A
88 A