Wire Size And Tightening Torque; Specifications - Toshiba 4200FA Series Operation Manual

Battery cabinet system for 4200fa series 15 & 25kva ups
Hide thumbs Also See for 4200FA Series:
Table of Contents

Advertisement

5.0
Battery System Connections
5.3

Wire Size and tightening torque

(Terminal Number)
Battery Control Circuit
6.0

Specifications

Power Circuit
Battery Voltage
Discharge Cut-off Voltage
Discharge Current
Nominal Run Time
Charging Voltage
Charging Current
Control Circuit
Shunt Trip Coil Voltage
Shunt Trip Coil Current
Auxiliary Contact Ratings
Environmental
Operating Temperature
Operating Humidity
Altitude
Mechanical
Dimensions
TOSHIBA
Wire Size and Tightening Torque
for Battery System Terminals (15 & 25kVA)
Terminal
Wire Size
14-16
(1-6)
Battery
3 AWG min.
(+ -)
350MCM max.
Ground
8 AWG min.
(GND)
13
15 & 25kVA
Tightening Torque
16 in-lbs.
150 in-lbs.
75 in-lbs.
288Vdc nominal
216Vdc min. (1.50Vdc/cell)
100Adc max.
15minutes min., 25kVA UPS at 100% load
30minutes min., 15kVA UPS at 100% load
328Vdc max.
5.5Adc max.
24Vdc nominal, 18Vdc min., 26.4Vdc max.
1.5A nominal
5Adc max. at 30Vdc
10Aac max. at 120Vac to 250Vac
°
°
0
C to 40
C; optimal temperature is 25
Less than 90% RH (non-condensing)
Less than 1000 meters
23.5 inch W, 33.7 inch D, 59.2 inch H
°