Wire Size And Tightening Torque - Toshiba UNINTERRUPTIBLE POWER SYSTEM 1600XP Installation And Operation Manual

Single phase - 3.6/6/8/10/14/18/22 kva
Hide thumbs Also See for UNINTERRUPTIBLE POWER SYSTEM 1600XP:
Table of Contents

Advertisement

Wire Size and Tightening Torque

Use the following table to select the recommended wire size and terminal lug tightening torque for i/o
wire connections. Use 90 °C copper conductors for all input, output, and ground wiring.
Terminal
Item
Number
AC input lines
1 and 2
AC output lines
4, 5, and 7
AC output neutral
6
ground
3 and 8
epo Switch
14 and 15
remote Switch
16 and 17
note: wire size is presented as the recommended size followed by a bold number in () that is the maximum wire
size the terminal block can accommodate. See page 64 for knock-out hole sizes on the back of each model.
14
Cable Size - AWG
3.6
6 kVA
8 kVA
10 kVA 14-18 kVA
kVA
10 (8)
8 (8)
(1/0)
8
6
(1/0)
12 (8)
10 (8)
8
6
(1/0)
12 (8)
10 (8)
8
6
12 (8)
10 (8)
(1/0)
8
6
16
16
16
16
16
16
22 kVA
(1/0)
4 (1/0)
1 (1/0)
(1/0)
4 (1/0)
1 (1/0)
(1/0)
)
1 (1/0)
4 (1/0)
(1/0)
)
1 (1/0)
4 (1/0)
16
16
16
16
16
16
1600Xp Series installation and operation manual
Tightening
Torque
lb.-in. (N•m)
14.2 (1.56)
14.2 (1.56)
14.2 (1.56)
14.2 (1.56)
9.0 (0.99)
9.0 (0.99)

Advertisement

Table of Contents
loading

This manual is also suitable for:

1600xp serie1600xp series

Table of Contents