The Device Configuration DIP Switch

Overview

4100 Comm. Baud Rate.
Switch (SWx-1)
Must Be Set to ON
Appendix A
Addressable cards include a bank of eight DIP switches. From left to right (see Figure A-
1, below) these switches are designated as SWx-1 through SWx-8. The function of these
switches is as follows:
SWx-1. This switch sets the baud rate for the internal 4100 communications line
running between the card and the CPU. Set this switch to ON.
SWx-2 through SWx-8. These switches set the card's address within the 4100
FACP. Refer to Table A-1 for a complete list of the switch settings for all of the
possible card addresses.
Note: You must set these switches to the value assigned to the card by the
4100 Programmer.
ON
OFF
DIP Switches SWx-2 through
SWx-8 set the Card Address.
Figure shows an Address of 3.
1
2
3
4
5
6
Figure A-1. DIP Switch SWx
A-1
7
8
Continued on next page