General
Fuses
Firmware Features
Appendix H
4100U Specifications
System Capacity
annunciation. Expansion
Cabinet Size
Cabinet Material
Cabinet Finish
Cabinet Colour
Mounting
Mains Input
Internal Power Supply
Standby Battery
Battery Charger
PSU Supervision
Temperature
Humidity
Refer to Table 6-1, 6-2 for full SPS specifications.
Alarm Relay Card
F1 Alarm, 3A, 15 x 5mm, Glass Cartridge
F2 Supervisory, 3A, 15 x 5mm, Glass Cartridge
F3 Trouble, 3A, 15 x 5mm, Glass Cartridge
Fused Distribution Board (if fitted)
F1 24V Out, 1A 20 x 5mm Glass Cartridge
F2 24V Out, 1A 20 x 5mm Glass Cartridge
F3 24V Out, 1A 20 x 5mm Glass Cartridge
F4 24V Out, 1A 20 x 5mm Glass Cartridge
•
WALK TEST System Test
•
4 Operator Access Levels
•
Event Historical Logging
•
Device selectable Alarm Verification
•
Individual Zone Isolate
•
Addressable device disable/enable
•
Non-volatile Flash EPROM for field editable program changes
•
Expansion cards firmware upgraded via download to flash EPROMs
2,000 points of addressable points, plus 2,000 points of
Up to capacity above.
Up to 119 Addressable cards
Dependent on system configuration
1.6mm Zintex
Powder coated
Cream Wrinkle
Wall mount
240V AC, +6%, -10%, 50Hz
24V DC @ 9A
24V sealed lead acid up 110Ah
27.3V DC (nominal)
Charger high/low, Battery low/fail
-5°C to 45°C
10% to 90% RH non-condensing
H-1