List of Approved Devices,

Compatible Detectors, IDNET

Continued
Simplex MAPNET 2 Range – Addressable Field Devices
2190-9156
2190-9162
2190-9164
2190-9169
2190-9172
2190-9173
Module
4099-9032NL
The following lists the detectors approved for use with IDNet and shows current
rating and numbers allowed per loop.
Device Type
4098-9714E
Analogue Photoelectric
Smoke Detector
4098-9717E
Analogue Ionisation
Smoke Detector
4098-9733E
Analogue Heat Type A &
B Detector
4098-9754E
Analogue Multi
(Heat/Photo)
Detector
* Maximum allowed by AS1670.1.
The above with 9714E, 9717E and 9733E use a (4098-) 9789E addressable base
or 9794E addressable sounder base, or 9793 addressable isolator base. The
9754E uses a 9796E addressable base or 9795E sounder base.
The maximum specified loop/line resistance is 40Ω.
The maximum number of LEDs switched on by an IDNet in alarm is 20.
Mapnet 2 Monitor ZAM
Mapnet 2 Signal ZAM
Mapnet 2 Control ZAM
Mapnet 2 Line Powered Short Circuit Isolator
Mapnet 2 Supervised IAM
Mapnet 2 Loop powered 2 Point Input / Output
Mapnet 2 Addressable Manual Call Point
Operating
Maximum
Current mA
Number Allowed
Per Loop
0.5
(2 with LED
on)
0.5
(2 with LED
on)
0.5
(2 with LED
on)
0.5
(2 with LED
on)
F-4
Maximum
Number
Allowed Per
Line
250
40*
250
40*
250
40*
250
40*