Compatible Addressable Field Devices, IDNet

The following lists the addressable devices approved for use with IDNet and
shows current rating and numbers allowed per loop.
Device Type
4090-9116
IDNet Comms Isolator
4090-9118
Relay IAM with T-sense
4090-9117
Addressable Power
Isolator
4090-9118
Relay IAM with T-Sense
Input
4090-9119
Relay IAM with
unsupervised Input
409-9120
6 Point I/O
4090-9001
Supervised IAM
4090-9101
Monitor ZAM
4099-9032
Manual Call Point
* Maximum allowed by AS1670.1.
The maximum specified loop/line resistance is 40Ω.
The maximum number of LEDs switched on by an IDNet in alarm is 20.
The 6 Point I/O LED is powered from the external 24V supply, not from the loop.
Note: The relays on the 6 Point I/O are not approved for switching field loads,
i.e. the
contacts may only be used to switch loads within an earthed
cabinet.
Operating
Maximum
Current mA
Addressable
Analogue Loop
0.5
(2 with LED on)
0.5
(2 with LED on)
0.5
(2 with LED on)
0.5
(2 with LED on)
0.5
(2 with LED on)
0.5
0.65
(2.8 with LED
on)
0.65
(2.8 with LED
on)
0.65
(2.8 with LED
on)
F-5
Maximum
Addressable
Point On
Points on
Analogue Line
250
40*
250
40*
250
40*
250
40*
250
40*
250
40*
250
40*
250
40*
250
40*