The Terminal Block Utility Module (4100U)

Overview

Mounting to the
Electronics Bay
SCREW HOLES FOR
MODULE BRACKET
TERMINAL BLOCK UTILITY MODULE
The 4100-0632 Terminal Block Utility Module is an all-purpose terminal block that
mounts to an expansion bay, above or below the power distribution interface (PDI). Each
module utilizes one block of mounting space.
The terminal block utility module has two 16-position terminal blocks that accept up to a
maximum of 12 AWG (3.309 mm
Follow the directions below to mount the terminal block utility module to the electronics
bay.
1. Align the terminal block utility module to any two compatible screw holes on the
electronics bay. Position the higher terminal block towards the middle of the
bay. There are eight possible locations: four above and four below the PDI.
Refer to the figure, below.
2. Secure the terminal block utility module to the electronics bay with two #6
screws and lockwashers.
3. The shorting strip may be removed or modified, depending on the application.
#6 SCREW AND LOCKWASHER

Figure 2-20. Terminal Block Utility Module Mounting

2
) wire.
2-27