Notes; Class A Wiring; Figure 8-5. Class A Wiring; Table 8-2 Cable Run Lengths - Simplex 4100U Installation & Maintenance

Fire indicator panel, fire alarm system
Hide thumbs Also See for 4100U:
Table of Contents

Advertisement

Wiring to IDNet Devices,
Wire Size
Distance
Distance

Notes

Class A Wiring

Continued

Table 8-2 Cable Run Lengths

2
0.75 mm
1 mm
385 m
513 m
769 m
1,026 m
1. The circuit allowance per device on the loop is 0.5mA with the LED off, 2mA with
the LED
on. A maximum of 20 LEDs get turned on at one time by IDNet Card (i.e.
in alarm).
2. The minimum voltage allowed at the furthest device to guarantee operation is
24.9Vdc. The
IDNet boosts its output voltage from nominal 30V to nominal 35V during alarm.
To connect the IDNet card to devices using Class A wiring, read the following
instructions and refer to the figure below.
1. Route wire between 0.75 mm
on TB1 of
the IDNet card to the appropriate inputs on a peripheral IDNet device.
2. Route wire from the first IDNet device to the next one. Repeat for each
appliance.
3. Route wire from the last IDNet device to the IDNetA+ and IDNetA- inputs on
TB1 of the IDNet card.
4. Separate every 40 devices (maximum) with a coms isolator (e.g. 4090-9116).
5. Separate sounder bases or 6 point I/O modules in zones using the 4090-9117 Power
Isolate module.
IDNET DEVICES
1
2
2
mm
mm
0.75
to 4
FERRITE BEAD
IDNET CARD
2
2
1.5 mm
2.5 mm
769 m
1,282 m
1,538 m
2,565 m
2
2
and 4 mm
from the IDNetB+, IDNetB- outputs
2
1
2
SHIELD

Figure 8-5. Class A Wiring

8-8
2
2
4 mm
Resistance
2,052 m
20Ω
4,104 m
40Ω
1
2
+
SHIELD
Continued on next page
FERRITE BEAD
(see fig 7.1)