Temperature And Humidity Operating Standards; Thermal Protection Features - HP L1000 - 9000 - 0 MB RAM User Manual

User guide - hp rp5400 family of servers
Hide thumbs Also See for L1000 - 9000 - 0 MB RAM:
Table of Contents

Advertisement

System Specifications

Temperature and Humidity Operating Standards

Temperature and Humidity Operating Standards
The following table lists the temperature and humidity specifications for rp54xx servers.
Operational
Parameter
a
o
Temperature
5
C to 35
o
(41
Operating
15 to 80%
Humidity
Relative
humidity
(Non-condensing)
at 35
a. The rp54xx has been designed to operate within the above specific temperature and relative
humidity operational limits. In general, operating any electronic equipment within the
recommended ranges of temperature and humidity will produce optimal reliability.
b. Temperature ranges stated above are at sea level. Maximum operating temperature is
derated (reduced) by 2
meters.
Operating ranges refer to the ambient air temperature and humidity measured at the cabinet
NOTE
cooling air intake vents.

Thermal Protection Features

If the cabinet temperature approaches 35
message will be displayed on the system console. At 40
190
Temperature and Humidity Specifications
Recommended
Operating
Limits
Range
o
o
C
20
C to 25
o
b
o
F to 95
F)
(68
F to 77
40 to 60%
Relative
humidity
(Non-condensing)
o
o
C (95
F)
o
C for each 1000 meters above sea level up to a maximum of 3000
o
C, thermal protection will be invoked. At 35
Maximum
Rate of Change
(per hour)
o
o
o
C
10
C (50
F) per
hour (With tape
o
F)
media)
o
o
20
C (68
F) per
hour (Without
tape media)
30% Per hour
Relative humidity
(Non-condensing)
o
o
C +/- 2
C an ungraceful shutdown will occur.
Non-Operating
Ranges
o
o
-40
C to +70
C
o
o
(-40
F to +158
F)
90% Relative
humidity
(Non-condensing)
o
o
at 65
C (149
F)
o
o
C +/- 2
C a warning
Appendix B

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rp5400

Table of Contents