Source/Circuit
type
Single-phase 63 A
Single-phase 30 A
More information
Generic Site Preparation Guide

Environmental specifications

Temperature and humidity specifications

The following table contains the allowed and recommended temperature and humidity limits for both
operating and nonoperating Integrity Superdome X systems.
Specification
Temperature range
Allowable Operating Range
Recommended Operating Range
Nonoperating (powered off)
Nonoperating (storage)
Humidity Range (noncondensing)
Allowable Operating Range
Recommended Operating Range
Nonoperating (powered off)
Nonoperating (storage)
1
All temperature ratings shown are for sea level. An altitude derating of 1° C per 300 m above 900 m is
applicable. No direct sunlight allowed. Upper operating limit is 3,048 m (10,000 ft) or 70 Kpa/10.1 psia.
Upper nonoperating (storage) limit is 9,144 m (30,000 ft) or 30.3 KPa/4.4 psia.
2
The Recommended Operating Range is recommended for continuous operation. Operating within the
Allowable Operating Range is supported but might result in a decrease in system performance.
28
Environmental specifications
Source voltage
Plug or connector
(nominal)
type
200–240 VAC
IEC 309 63 A
Single Phase Blue,
50/60 Hz
3.6 m (11.8 ft)
power cord
200–240 VAC
NEMA L6-30P
Single Phase,
50/60 Hz
3.6 m (11.8 ft)
power cord
1
2
Power receptacle
required
IEC 309 63 A
Single Phase, Blue
NEMA L6-30R
Single Phase
Value
+5° C to +40° C (41° F to 104° F)
+18° C to +27° C (64° F to 81° F)
+5° C to +45° C (41° F to 113° F)
-40° C to +80° C (-40° F to 176° F)
-12° C DP and 8% RH to +24° C DP and 85% RH
+5.5° C DP to +15° C DP and 65% RH
8% RH to 90% RH and 29° C DP
8% RH to 90% RH and 32° C DP
Number of power
cords required
(per enclosure
leaving the rack)
4
6