IBM 7870B4U Service Manual page 145

Problem determination and service guide
Table of Contents

Advertisement

v Follow the suggested actions in the order in which they are listed in the Action column until the problem is
solved.
v See Chapter 4, "Parts listing," on page 41 to determine which components are CRUs and which components
are FRUs.
v If an action step is preceded by "(Trained service technician only)," that step must be performed only by a
trained service technician.
Error Code
Type
0x806F0413
Error
Error Message
Group 2 (All PCI Err) PCI parity
error;
Action
1. Verify that you have the latest system firmware
(see "Firmware updates" on page 34).
2. If an expansion card is installed in the blade
server, verify that the firmware for each
expansion card is up to date.
3. Run the Setup utility and restore system setting to
defaults (see "Using the Setup utility" on page
21).
4. Check the event logs for other related error
messages (see "Error logs" on page 103).
5. Reseat any expansion cards that are installed in
the blade server (see "Removing an I/O
expansion card" on page 71 and "Installing an
I/O expansion card" on page 75).
6. Remove each expansion card, one at a time until
the error does not occur (see "Removing an I/O
expansion card" on page 71).
7. Replace failing adapter and reinstall any other
expansion cards that were removed (see
"Installing an I/O expansion card" on page 75).
8. (Trained service technician only) If the error
continues, replace the system-board assembly (see
"Removing the system-board assembly" on page
97 and "Installing the system-board assembly" on
page 98).
131
Chapter 6. Diagnostics

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bladecenter hs22787019361911

Table of Contents