Temperature checkout

Proper cooling of the system is important for proper operation and system
reliability. For a typical xSeries server/workstation, you should make sure:
v Each of the drive bays has either a drive or a filler panel installed
v The top cover is in place during normal operation
v There is at least 50 mm (2 inches) of ventilated space at the sides of the
v The top cover is removed for no longer than 30 minutes while the
v A removed hot-swap drive is replaced within two minutes of removal
v Cables for optional adapters are routed according to the instructions provided
v The fans are operating correctly and the air flow is good
v A failed fan is replaced within 48 hours
In addition, ensure that the environmental specifications for the system are met.
See "Features and specifications" on page 4.
Note: The server/workstation is not designed to operate in an enclosed
For more information on specific temperature error messages, see "Temperature
error messages" on page 131.
parameters.
v Set the system date and time.
v Set the power-on password.
v Reconfigure the server/workstation.
server/workstation and 100 mm (4 inches) at the rear of the server/workstation
server/workstation is operating
with the adapters (ensure that cables are not restricting air flow)
environment. The xSeries 330 should not reside behind a glass door in its
rack enclosure.