600-W Protection Circuits - Intel SC5300BRP Technical Product Specification

Server chassis 5u kit
Hide thumbs Also See for SC5300BRP:
Table of Contents

Advertisement

Intel® Server Chassis SC5300 5U Kit TPS
(2) Peak load on the combined 12V output shall not exceed 48A.
(3) Maximum continuous load on the combined 12V output shall not exceed 43A.
(4) Peak total DC output power should not exceed 660W.
(5) Peak power and peak current loading shall be supported for a minimum of 12 seconds.
3.1.5.3
Voltage Regulation
The output voltages must stay within the following voltage limits when operating at steady state
and dynamic loading conditions. These limits include the peak-peak ripple/noise. All outputs are
measured with reference to the return remote sense signal (ReturnS). The +12V3, +12V4, –12V
and 5VSB outputs are measured at the power supply connectors referenced to ReturnS. The
+3.3V, +5V, +12V1, and +12V2 are measured at the remote sense signal located at the signal
connector.
PARAMETER
+3.3V
+5V
+12V1
+12V2
+12V3
+12V4
- 12V
+5VSB
3.1.5.4
Standby Operation
The 5V standby output is present when an AC input greater than the power supply turn on
voltage is applied.
The power supply fan is off (fan-less operation) when the power supply is in the stand-by mode
of operation. The power supply will work indefinitely in stand-by mode with the input AC power
on, power supply off, and the 5V stand-by output at full load (=2A).
3.1.6

600-W Protection Circuits

Protection circuits inside the power supply shall cause only the power supply's main outputs to
shutdown. If the power supply latches off due to a protection circuit tripping, an AC cycle OFF
for 15 sec and a PSON# cycle HIGH for 1 sec shall be able to reset the power supply.
Revision 1.31
Table 13. Voltage Regulation Limits
TOLERANCE
MIN
- 5% / +5%
+3.14
- 5% / +5%
+4.75
- 5% / +5%
+11.40
- 5% / +5%
+11.40
- 5% / +5%
+11.40
- 5% / +5%
+11.40
- 5% / +9%
- 11.40
- 5% / +5%
+4.75
Chassis Power Subsystem
NOM
MAX
+3.30
+3.46
+5.00
+5.25
+12.00
+12.60
+12.00
+12.60
+12.00
+12.60
+12.00
+12.60
-12.00
-13.08
+5.00
+5.25
UNITS
V
rms
V
rms
V
rms
V
rms
V
rms
V
rms
V
rms
V
rms
31