proper airflow for all installed equipment, since duct system changes
may occur at any time, such as opened or closed registers.
This option allows the installer to select the airflow for the fan coil when
paired with a hydronic coil. After the selections are made, touch SAVE.
• Airflow: Selectable between Off to Max in 50 CFM increments.
Default = Off, 500 CFM, Max = (odu_size in KBTU * 400/12)
NOTE: Selected airflow used during hydronic heating is a fixed value, it
does not vary.
• Blower On Delay: Selectable from 0 to 240 seconds. Default = 30
seconds
• Blower Off Delay: Selectable from 0 to 240 seconds. Default = 0
seconds