6.3.1.5. Scheduling On/Off
This option lets the installer allow comfort schedule programming
features. After the selection is made, touch SAVE.
• Scheduling: On or Off. Default = On
6.3.1.6. Smart Recovery On/Off
NOTE: "Smart Recovery" refers to transitions between and among the
Home, Sleep and Wake modes. Moving from the Away mode to any
other mode is covered by the "Advanced Smart Setback" feature.
Smart Recovery applies to programmable operation only. Smart
Recovery causes the system to ramp the system target setpoints to those
for the next programmed schedule period to help save energy during
period transitions. Smart Recovery will start recovery 90 minutes prior to
schedule change in both heating and cooling mode. After the selection is
made, touch SAVE.
• Smart Recovery: On or Off. Default = On
NOTE: The "Temperature Units Display" set-up section has been moved
to the Homeowner Screens. See the Owner's Manual for more
information.
6.3.2. Fan Coil
First touch SETUP, then touch FAN COIL to set up the parameters for
the fan coil unit.
6.3.2.1. Airflow
This option allows the installer to select the appropriate air flow based on
the needs of the installation. The QUIET airflow means the minimum
cooling airflow that the system can safely run (typically 300 CFM/ton).
Use this setting if duct noise is a severe problem. Note that duct sweating
in high humidity environments could become an issue at low airflows.
The COMFORT airflow means airflow is varied depending on humidity
33