terminals on the Evolution System compressor section control board to
receive a dry contact relay signal from the Utility, typically from the
electric meter assembly, to signal a curtailment period. This section
describes the actions taken in response to that signal. See the equipment
installation instructions for more information on wiring the compressor
section control board to the Utility connections.
Utility Saver is used to force the equipment to a lower stage (low or off)
when activated by the utility company, typically during peak load times.
This setup is available only if the equipment has a utility saver input
(refer to outdoor equipment installation instructions). This setup controls
the response of the equipment when the utility saver input is active.
DISABLED means that the curtailment function is not active. TURN
OFF means the outdoor unit is to be turned off when the curtailment
function is active. LOW STAGE means the outdoor unit will run in lows
stage when the curtailment function is active. After the selections are
made, touch SAVE.
A12193
• Cooling: Disabled, Low Stage or Turn off. Default = Disabled
• Heat Pump: Disabled, Low Stage or Turn off. Default = Disabled
6.3.11. Hydronic Airflow
NOTE: The daily duct assessment will occur even if Hydronic Airflow is
set to Off. This is done to ensure that the system will continue to provide
55