open-loop systems using untreated water; and 15°F is chosen for
closed-loop systems using glycol or other anti-freeze solutions. After the
selection is made, touch SAVE.
• Freeze Limits: 26°F or 15°F. Default = 26°F
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
Only use 15F setting if loop is treated with anti-freeze
provisions.
6.3.7.2. Lockout Count
This setting controls the number of times within an hour that the HPS or
LPS trips before the Geo HP compressor will lockout for four hours.
After the selection is made, touch SAVE.
• Lockout Count: 4 or 2
• Default = 2