mode will result in higher energy usage but benefit the customer with
greater comfort.
6.3.1.2. Heat/Cool Deadband
The minimum difference enforced between heating and cooling desired
temperatures. The deadband does not change when the user changes
between Fahrenheit (°F) and Celsius (°C). Ex: A 2° deadband will be 2°F
or 2°C and does not change with units, °F and °C. This can allow one
setting to "push" the other to maintain this difference. When the correct
deadband is set, touch SAVE.
• Deadband: Adjustable from 0 to 6°. Default = 2°
6.3.1.3. Offsets
This option allows calibration (or deliberate miscalibration) of the
temperature and humidity sensors. These offsets are added to the actual
temperature/humidity values. See also Zone Offsets Section. When the
correct offsets are made, touch SAVE. If the system is non-zoned, the
indoor temperature offset is found on this screen. If the system is zoned,
the indoor temperature offset is found in the Zoning, Offsets screen.
• Outdoor temperature: Adjustable from -5 to 5°F (-3 to 3°C).
Default = 0°F
• Indoor temperature: Adjustable from -5 to 5°F (-3 to 3°C).
Default = 0°F