Configuring Outlet Power Thresholds
Click the outlet power thresholds link at the bottom of the Outlets page to display the configuration page:
To set outlet power thresholds:
1. Provide the threshold hysteresis between event state and recovery (W). Range is 0-1000W; default is 10W.
2. Set the low/high alarm and low/high warning threshold values (W) for outlet power (without power factor).
Range is min 0W, max is power capacity in ostat details command.
3. Click Apply.
Using the Web Interface
Switched PRO2 – User Guide
71