Parameters
The set loadshed command uses the following parameters:
Sub-Parameters
The set loadshed command uses the following sub-parameters:
Usage Guidelines
The Smart Load Shedding feature must be enabled.
Command Access
Admin level only

set location

Sets the system location string.
Command Syntax
set location <location string>
Parameters
The set location command uses the following parameter:
Command Access
Admin level only
Using the Command Line Interface (CLI)
branch
Sets to allow branch shedding events.
line
Sets to allow line shedding events.
sensor
Sets to allows sensor shedding events.
ups
Sets to allow UPS shedding events.
all
Sheds outlets only when all UP devices on an upstream line go to "on
battery".
any
Sheds outlets when any UPS device on an upstream line goes to "on
battery".
recoverdelay
The delay that a UPS device needs to be "on utility" before recovering
outlets. 0-10 minutes.
recovery off
Shed outlets are not recovered Does not recover shed outlets when
even conditions are cleared.
recovery on
Automatically recover shed outlets when event conditions are cleared.
sheddelay
The delay that a UPS device needs to be "on battery" before shedding
outlets. 0-10 minutes.
location string
Location string text for system location. 0-63 characters.