set sensor
Sets sensor configuration values.
Command Syntax
set sensor adc [alarmhi | alarmlo | warnhi | warnlo] <name | id | ALL> <value>
set sensor adc email [disabled | enabled] <name | id | ALL>
set sensor adc hyst <value>
set sensor adc name <name | id> <name>
set sensor adc snmpt [disabled | enabled] <name | id | ALL>
set sensor contact email [disabled | enabled] <name | id | ALL>
set sensor contact name <name | id> <name>
set sensor contact snmpt [disabled | enabled] <name | id | ALL>
set sensor humid [alarmhi | alarmlo | warnhi | warnlo] <name | id | ALL> <value>
set sensor humid email [disabled | enabled] <name | id | ALL>
set sensor humid hyst <value>
set sensor humid name <name | id> <name>
set sensor humid snmpt [disabled | enabled] <name | id | ALL>
set sensor temp [alarmhi | alarmlo | warnhi | warnlo] <name | id | ALL> <value>
set sensor temp email [disabled | enabled] <name | id | ALL>
set sensor temp hyst <value>
set sensor temp name <name | id> <name>
set sensor temp snmpt [disabled | enabled] <name | id | ALL>
set sensor water email [disabled | enabled] <name | id | ALL>
set sensor water name <name | id> <name>
set sensor water snmpt [disabled | enabled] <name | id | ALL>
set sensor temp scale [celsius | fahrenheit]
Parameters
The set sensor command uses the following parameters:
Using the Command Line Interface (CLI)
adc
Sets the analog-to-digital converter sensor. min 0, max 255, hyst 0-20
(default 1).
contact
Sets the contact closure sensor.
humid
Sets the humidity sensor. min 0%RH, max 100%RH, hyst 0-20%RH
(default 2%RH).
temp
Sets temperature sensor. For Celsius: min -40°, max 123°, hyst 0-30°,
default 1°; For Fahrenheit: min -40°, max 253°, hyst 0-54°, default 2°.
water
Sets the water sensor.
email
Sets the email notifications for sensor events.
hyst
Sets the hysteresis between event state and recovery.
name
Sets the name of the sensor.
snmpt
SNMP trap notifications for sensor events.
scale
Sets temperature scale.
Switched PRO2 – User Guide
•
171
Need help?