8 Parameters
[2]
USB Port
[3] *
Option A
[4]
Option B
[5]
Option C0
[6]
Option C1
NB!
This parameter cannot be adjusted while the motor is running.
8-03 Cont r ol Tim eout Tim e
Range:
60.0 s*
[1.0 - 18000.0 s]
8
8- 04 Cont r ol Tim eout Funct ion
Opt ion:
[0] *
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and trip
[7]
Select setup 1
[8]
Select setup 2
[9]
Select setup 3
[10]
Select setup 4
[20]
N2 Override Release
In LonWorks, the time-out function is also activated when the following SNVT's fail to be updated within the time period specified in par.8-03
Timeout Time
:
nviStartStop
nviReset Fault
nviControlWord
50
Funct ion:
Enter the maximum time expected to pass between the reception of two consecutive telegrams. If
this time is exceeded, it indicates that the serial communication has stopped. The function selected
in par.8-04
Control Timeout Function Control Time-out Function
In LonWorks the following variables will trigger the Control Word Time parameter:
nviStartStop
nviReset Fault
nviControlWord
nviDrvSpeedStpt
nviRefPcnt
nviRefHz
Funct ion:
Select the time-out function. The time-out function is activated when the control word fails to be
updated within the time period specified in par.8-03
after setting the N2 protocol.
nviDrvSpeedStpt
nviRefPcnt
nviRefHz
®
MG.11.E2.02 - VLT
is a registered Danfoss trademark
VLT® FC 100 LonWorks
will then be carried out.
Control Timeout Time
. Choice [20] only appears