5 Configuration of the system
5.5 Net w or k Var iable Descr ipt ion - VSD Pr of ile - Out put
5.5.1 Dr ive Speed
Variable
nam e:
nvoDrvSpeed
This variable contains the frequency converter speed as a percentage of the nominal speed.
5.5.2 Out put Cur r ent
5
Variable
nam e:
nvoDrvCurnt
This variable contains the frequency converter output current in ampere measured as a mean value, IRMS.
The value is filtered and therefore approximately 1.3 seconds delayed before a current change is reflected in the output variable.
5.5.3 Out put Volt age
Variable
nam e:
nvoDrvVolt
This variable contains the frequency converter output voltage.
5.5.4 Out put Pow er
Variable
nam e:
nvoDrvPwr
This variable contains the frequency converter output power in kW, calculated on the basis of the actual motor voltage and current.
The value is filtered and therefore approximately 1.3 seconds delayed before a power change is reflected in the output variable.
5.5.5 Running Hour s
Variable
nam e:
nvoDrvRunHours
This variable contains the total running hours of the motor.
36
SNVT
t ype:
SNVT_lev_percent
SNVT
t ype:
SNVT_amp
SNVT
t ype:
SNVT_volt
SNVT
t ype:
SNVT_power_kilo
SNVT
t ype:
SNVT_time_hour
MG.11.E2.02 - VLT
Value:
Min:
Max :
-163.840 %
+163.830 %
Value:
Min:
Max:
0 A
3,276.6 A
Value:
Min:
Max :
0 V
3,276.6 V
Value:
Min:
Max:
0 kW
6,554.4 kW
Value:
Min:
Max :
0 hr
65,534 hr
®
is a registered Danfoss trademark
VLT® FC 100 LonWorks
Resolut ion:
0.005 %
Resolut ion:
0.1 A
Resolut ion:
0.1 V
Resolut ion:
0.1 kW
Resolut ion:
1 hr