5 Configuration of the system
5.6.5 Min Ram p-up Tim e [ s]
Variable
nam e:
nciRampUpTime
This variable configures the Ramp 1 ramp-up time and associates it with par. 3-41
5.6.6 Min Ram p-dow n Tim e [ s]
Variable
5
nam e:
nciRampDownTime
This variable configures the Ramp 1 ramp-down time and compares it with par. 3-42
5.6.7 Hear t beat Tim e [ s]
Variable
nam e:
nciSndHrtBt
This variable configures a heartbeat timer to send the following variables:
nvoDrvCurnt
nvoDrvSpeed
nvoDrvVolt
nvoDrvPwr
Setting the timer to 0.0 disables the timer.
Heartbeat timers have the purpose of sending out heartbeat signals containing specific data, enabling management systems to prove that the node is
present on the network and working correctly. Only bound variables will be transmitted.
38
SNVT
Def ault value:
t ype:
SNVT_time_sec
SNVT
Def ault value:
t ype:
SNVT_time_sec
SNVT
Default value:
t ype:
SNVT_time_sec
MG.11.E2.02 - VLT
Min value:
10 s
1 s
Ramp 1 Ramp Up Time
.
Min value:
10 s
1 s
Ramp 1 Ramp Down Time
Min value:
0 s
0 s
®
is a registered Danfoss trademark
VLT® FC 100 LonWorks
Max value:
3,600 s
Max value:
3,600 s
.
Max value:
6,553.4 s

Advertisement