Omron CJ - PROGRAMMING MANUAL 08-2008 Programming Manual page 267

Programmable controllers
Hide thumbs Also See for CJ - PROGRAMMING MANUAL 08-2008:
Table of Contents

Advertisement

Manipulating Files
Operations Continuing
during and after Program
Replacement
Operations after
Program Replacement
Time Required for
Program Replacement
Related Auxiliary Bits/Words
Name
File Memory Operation Flag
Memory Card Detected Flag
(Not supported by CS-series
pre-EV1 CS1 CPU Units)
IOM Hold Bit
Forced Status Hold Bit
When the IOM Hold Bit (A50012) is ON, the data in the following memory
areas will be maintained: the CIO Area, Work Area (W), Timer Completion
Flags (T), Index Registers (IR), Data Registers (DR), and the current EM bank
number.
Note Timer PVs will be cleared during program replacement.
If the IOM Hold Bit is ON when the program is transferred, loads that were
being output before program replacement will continue to be output after
replacement. Be sure that external loads will operate properly after program
replacement.
The status of force-set and force-reset bits will be maintained through the pro-
gram replacement if the Forced Status Hold Bit (A50013) is ON.
Interrupts will be masked.
If data tracing is being performed, it will be stopped.
Instruction conditions (interlocks, breaks, and block program execution) will be
initialized.
Differentiation Flags will be initialized whether the IOM Hold Bit is ON or OFF.
The status of the cyclic tasks depends upon their operation-start properties.
(Their status is the same as it would be if the PLC were switched from PRO-
GRAM to RUN/MONITOR mode.)
The First Cycle Flag (A20011) will be ON for one cycle after program execu-
tion resumes. (The status is the same as it would be if the PLC were switched
from PROGRAM to RUN/MONITOR mode.)
Size of entire program
60 Ksteps
250 Ksteps
Address
A34313
ON for any of the following:
The CPU Unit has sent a FINS command to itself using CMND(490).
FREAD(700) or FWRIT(701) are being executed.
The program is being overwritten using an Auxiliary Area control bit
(A65015).
A simple backup operation is being performed.
A34315
ON when a Memory Card has been detected.
A50012
When this bit is ON, the contents of I/O memory are retained through pro-
gram replacement.
A50013
When this bit is ON, the status of force-set and force-reset bits is main-
tained through program replacement.
Peripheral servicing time
set in PLC Setup
Default (4% of cycle time)
Operation
Section 5-2
Approx. time required for
program replacement
6 s
25 s
229