Cip Object Services; Cip Objects Sent To The Built-In Ethernet/Ip Port; Identity Object (Class Id: 01 Hex) - Omron Sysmac NJ-series User Manual

Machine automation controller cpu unit built-in ethernet/iptm port
Hide thumbs Also See for Sysmac NJ-series:
Table of Contents

Advertisement

8-5

CIP Object Services

This section shows services that specify the CIP object in the Request Path and access the CIP mes-
sage server function of the NJ/NX-series Controllers.
8-5-1

CIP Objects Sent to the Built-in EtherNet/IP Port

The following CIP objects can be sent to an EtherNet/IP port.
Object name
Identity object
TCP/IP interface object
Ethernet link object
Controller object
8-5-2

Identity Object (Class ID: 01 Hex)

This object reads the ID information of the CPU Unit and resets the built-in EtherNet/IP port. When
using an NX701 CPU Unit, use the route path to specify the port number (1 or 2) of the built-in Ether-
Net/IP port to access.
Service Codes
Specify the service to execute with the service code.
Service
Parameter name
code
01 hex
Get_Attribute_All
0E hex
Get_Attribute_Single
05 hex
Reset
*1 The value is 01 hex for a CPU Unit with unit version 1.09 or earlier.
Class ID
Specify 01 hex.
Instance ID
Specify 00 or 01 hex.
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User's Manual (W506)
• Reads ID information from the CPU Unit.
• Resets the built-in EtherNet/IP port.
• Writes and reads TCP/IP settings.
• Reads Ethernet settings.
• Reads Ethernet status.
• Gets the Controller status.
• Changes the operating mode of the Controller.
Description
Reads the values of the attributes.
Reads the value of the specified attribute.
Resets the built-in EtherNet/IP port. This parameter is used to reset
the built-in EtherNet/IP port when you change the IP address or
other parameter settings and want to apply them. Input one of the
following values for the ServiceDat input variable to the CIPSend
instruction to specify the reset method.
00 hex:
Resets the built-in EtherNet/IP port.
*1
02 hex
: Clears the saved tag data link settings and resets the
built-in EtherNet/IP port.
8 CIP Message Communications
Function
Classes
Supported.
Supported.
Not sup-
Reference
page 8-47
page 8-50
page 8-53
page 8-58
Supported services
Instances
Supported.
Supported.
Supported.
ported.
8-47