Cable Types - ABB ACS800-U1 Hardware Manual

Hide thumbs Also See for ACS800-U1:
Table of Contents

Advertisement

122 Technical data
ACS800-U1
Frame size
type
Three-phase supply voltage 525 V, 575 V, 600 V
-0011-7
R4
-0016-7
R4
-0020-7
R4
-0025-7
R4
-0030-7
R4
-0040-7
R4
-0050-7
R5
-0060-7
R5
-0070-7
R6
-0100-7
R6
-0120-7
R6
-0145-7
R6
-0175-7
R6
-0205-7
R6
* Type not available any more.

Cable types

Cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire
insulation at 40 °C (104 °F) ambient temperature. Not more than three current-
carrying conductors in raceway or cable or earth (directly buried). For other
conditions, dimension the cables according to local safety regulations, appropriate
input voltage and the load current of the drive.
Copper cables with concentric copper
Max. load
Input
current
A
A
10
20
13
20
19
30
21
30
29
45
32
45
45
70
51
80
70
100
82
125
103
150
121
200
150
200
188
250
shield
Cable type
current
A
AWG/MCM
18
22
31
44
57
75
88
101
114
132
154
176
202
224
250 MCM or 2 × 1
251
300 MCM or 2 × 1/0
Fuse
V
Manufacturer
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
00096931
Type
UL class
JJS-20
T
JJS-20
T
JJS-30
T
JJS-30
T
JJS-45
T
JJS-45
T
JJS-70
T
JJS-80
T
JJS-100
T
JJS-125
T
JJS-150
T
JJS-200
T
JJS-200
T
JJS-250
T
00096931, 00556489