108 Technical data
ACS800-01
Nominal
size
ratings
I
cont.max
A
Three-phase supply voltage 525 V, 550 V, 575 V, 600 V, 660 V or 690 V
-0011-7
13
-0016-7
17
-0020-7
22
-0025-7
25
-0030-7
33
-0040-7
36
-0050-7
51
-0060-7
57
-0070-7
79
-0100-7
93
-0120-7
113
-0145-7
134
-0175-7
166
-0205-7
190
1) These values are not calculated according to the ecodesign standard IEC 61800-9-2.

Symbols

Nominal ratings
I
continuous rms output current. No overload capability at 40 °C (104 °F).
cont.max
I
maximum output current. Available for 10 s at start, otherwise as long as allowed by
max
drive temperature.
Typical ratings:
No-overload use
P
typical motor power. The power ratings apply to most IEC 60034 motors at the
cont.max
nominal voltage, 230 V, 400 V, 500 V or 690 V.
Light-overload use (10% overload capability)
I
continuous rms current. 10% overload is allowed for one minute every 5 minutes.
2N
P
typical motor power. The power ratings apply to most IEC 60034 motors at the
N
nominal voltage, 230 V, 400 V, 500 V or 690 V.
Heavy-duty use (50% overload capability)
I
continuous rms current. 50% overload is allowed for one minute every 5 minutes.
2hd
P
typical motor power. The power ratings apply to most IEC 60034 motors at the
hd
nominal voltage, 230 V, 400 V, 500 V or 690 V.

Sizing

The current ratings are the same regardless of the supply voltage within one voltage
range. To achieve the rated motor power given in the table, the rated current of the
drive must be higher than or equal to the rated motor current.
Note 1: The maximum allowed motor shaft power is limited to 1.5 ·
P
(whichever value is greatest)
cont.max
current are automatically restricted. The function protects the input bridge of the
drive against overload. If the condition exists for 5 minutes, the limit is set to
P
.
cont.max
Note 2: The ratings apply at an ambient temperature of 40 °C (104 °F). At lower
temperatures the ratings are higher (except
Note 3: Use the DriveSize PC tool for a more accurate dimensioning if the ambient
temperature is below 40 °C (104 °F) or the drive is loaded cyclically.
Light-overload
No-
overload
use
use
I
I
P
max
cont.max
2N
kW
A
A
14
11
11.5
19
15
15
28
18.5
20
38
22
23
44
30
30
54
30
34
68
45
46
84
55
52
104
75
73
124
90
86
172
110
108
190
132
125
245
160
155
245
160
180
Heavy-duty use Frame
P
I
N
2hd
kW
A
7.5
8.5
5.5
11
11
7.5
15
15
11
18.5
19
15
22
22
18.5
30
27
22
37
34
30
45
42
37
55
54
45
75
62
55
90
86
75
110
95
90
132
131
110
160
147
132
.
If the limit is exceeded, motor torque and
I
).
max
Air flow Heat dis-
size
P
hd
3
kW
m
/h
R4
103
R4
103
R4
103
R4
103
R4
103
R4
103
R5
250
R5
250
R6
405
R6
405
R6
405
R6
405
R6
405
R6
405
P
,
1.1 ·
hd
(1
sipation
W
300
340
440
530
610
690
840
1010
1220
1650
1960
2660
3470
4180
0009693