124 Technical data

Input power connection

U
Voltage (
)
1
Short-circuit withstand
strength (IEC 60439-1)
Short-circuit current
protection (UL 508 C
CSA C22.2 No. 14-05)
Frequency
Imbalance
Fundamental power
factor (cos phi
)
1

Motor connection

U
Voltage (
)
2
Frequency
Frequency resolution
Current
Power limit
Field weakening point
Switching frequency
Maximum recommended
motor cable length

Efficiency

208/220/230/240 V AC 3-phase ± 10% for 230 V AC units
380/400/415 V AC 3-phase ± 10% for 400 V AC units
380/400/415/440/460/480/500 V AC 3-phase ± 10% for 500 V AC units
525/550/575/600/660/690 V AC 3-phase ± 10% for 690 V AC units
Maximum allowable prospective short-circuit current is 65 kA when
protected by fuses given in the
US and Canada: The drive is suitable for use on a circuit capable of
delivering not more than 100 kA rms symmetrical amperes at the drive
nominal voltage when protected by fuses given in the
fuse table.
48 to 63 Hz, maximum rate of change 17%/s
Max. ± 3% of nominal phase to phase input voltage
0.98 (at nominal load)
U
0 to
, 3-phase symmetrical, U
1
f
DTC mode: 0 to 3.2 ·
FWP
U
Nmains
f
=
· f
FWP
Nmotor
U
Nmotor
f
: frequency at field weakening point;
FWP
voltage;
U
: rated motor voltage;
Nmotor
0.01 Hz
IEC data
See
(page 106).
P
,
P
P
1.5 ·
1.1 ·
or
hd
N
cont.max
8 to 300 Hz
3 kHz (average). In 690 V units 2 kHz (average).
Sizing method
I
I
according to
and
2N
2hd
I
according to
at
cont.max
ambient temperatures
below 30 °C (86 °F)
I
according to
at
cont.max
ambient temperatures
above 30 °C (86 °F)
Note: With cables longer than 100 m (328 ft), the EMC Directive
requirements may not be fulfilled. See
Approximately 98% at nominal power level
The efficiency is not calculated according to the ecodesign standard
IEC 61800-9-2.
IEC data
(page 106) fuse tables.
at the field weakening point
max
. Maximum frequency 300 Hz.
U
Nmains
f
: rated motor frequency
Nmotor
(whichever value is greatest)
Max. motor cable length
DTC control
R2 to R3: 100 m (328 ft)
R4 to R6: 300 m (984 ft)
R2: 50 m (164 ft) Note: This applies to units with
EMC filter also.
R3 and R4: 100 m (328 ft)
R5 and R6: 150 m (492 ft)
CE marking
NEMA data
(page 119)
: mains (input power)
Scalar control
R2: 150 m (492 ft)
R3 to R6: 300 m (984 ft)
(page 128).