Symbols; Sizing; Derating - ABB ACS800-U1 Hardware Manual

Hide thumbs Also See for ACS800-U1:
Table of Contents

Advertisement

120 Technical data
I
ACS800-U1 size
max
Three-phase supply voltage 525 V, 575 V, 600 V
-0011-7
14
-0016-7
19
-0020-7
28
-0025-7
38
-0030-7
44
-0040-7
54
-0050-7
68
-0060-7
84
-0070-7
104
-0100-7
124
-0120-7
172
-0145-7
190
-0175-7
245
-0205-7
245
1) Overload may be limited to 5% at high speeds (> 90% speed) by the internal power limit of the drive.
The limitation also depends on motor characteristics and network voltage.
2) Overload may be limited to 40% at high speeds (> 90% speed) by the internal power limit of the
drive. The limitation also depends on motor characteristics and network voltage.
3) Special 4-pole high-efficiency NEMA motor
4) Higher rating is available with special 4-pole high-efficiency NEMA motor
5) Type not available any more.
6) These values are not calculated according to the ecodesign standard IEC 61800-9-2.

Symbols

Nominal ratings
I
maximum output current. Available for 10 s at start, otherwise as long as allowed by
max
drive temperature.
Normal use (10% overload capability)
I
continuous rms current. 10% overload is typically allowed for one minute every 5
2N
minutes.
P
typical motor power. The power ratings apply to most 4-pole NEMA rated motors
N
(230 V, 460 V or 575 V).
Heavy-duty use (50% overload capability)
I
continuous rms current. 50% overload is typically allowed for one minute every 5
2hd
minutes.
P
typical motor power. The power ratings apply to most 4-pole NEMA rated motors
hd
(230 V, 460 V or 575 V).
Note 1: The ratings apply at an ambient temperature of 40 °C (104 °F). In lower temperatures the
ratings are higher (except

Sizing

See page 108.

Derating

See page 109.
Normal use
I
P
2N
N
A
A
hp
11.5
10
15
10
20
15/20
23
20
30
25/30
34
30
46
40
52
50
73
60
86
75
108
100
125
125
155
150
192
200
I
).
max
Heavy-duty use
I
P
2hd
hd
A
hp
8.5
7.5
11
10
15
15
4)
2)
20
20
2)
25
25
4)
2)
30
30
2)
40
40
2)
42
40
54
50
62
60
86
75
99
100
131
125
147
150
Frame
Air flow
Heat dissi-
size
pation
3
ft
/min
R4
61
R4
61
R4
61
R4
61
R4
61
R4
61
R5
147
R5
147
R6
238
R6
238
R6
238
R6
238
R6
238
R6
238
(6
BTU/Hr
1050
1200
1550
1850
2100
2400
2900
3450
4200
5650
6700
9100
11850
14300
00096931