Alternate Short-Circuit Protection; Miniature Circuit Breakers (Iec) - ABB ACS180 Hardware Manual

Hide thumbs Also See for ACS180:
Table of Contents

Advertisement

104 Technical data
current
ACS180-04...
-15A6-2
-17A5-2
-25A0-2
-033A-2
-048A-2
-055A-2
3-phase U n = 440 ... 480 V
-01A8-4
-02A6-4
-03A3-4
-04A0-4
-05A6-4
-07A2-4
-09A4-4
-12A6-4
-17A0-4
-25A0-4
-033A-4
-038A-4
-045A-4
-050A-4

Alternate short-circuit protection

Miniature circuit breakers (IEC)

The protective characteristics of the circuit breakers depend on the type,
construction and settings of the breakers. There are also limitations pertaining
to the short-circuit capacity of the supply network. Your local ABB representative
can help you in selecting the breaker type when the supply network characteristics
are known.
WARNING!
Due to the inherent operating principle and construction of circuit breakers,
independent of the manufacturer, hot ionized gases can escape from the
breaker enclosure in case of a short-circuit. To ensure safe use, pay special
attention to the installation and placement of the breakers. Obey the
manufacturer's instructions.
Input
Min. short-cir-
cuit current
A
A
19.2
581
23.6
656
27.2
400
35
504
48
800
60
800
2.8
47
3.6
59
4.6
87
6.3
116
9.1
174
12
230
13
258
17.4
440
25.2
560
31.8
400
40.9
504
49
640
55.7
800
55.7
800
Nominal
Voltage
current
rating
A
V
30
300
35
300
40
300
50
300
70
300
80
300
6
600
6
600
10
600
10
600
20
600
20
600
25
600
30
600
35
600
40
600
60
600
70
600
70
600
70
600
Buss-
mann
Type
type
JJN-30
UL class T
JJN-35
UL class T
JJN-40
UL class T
JJN-50
UL class T
JJN-70
UL class T
JJN-80
UL class T
JJS-6
UL class T
JJS-6
UL class T
JJS-10
UL class T
JJS-10
UL class T
JJS-20
UL class T
JJS-20
UL class T
JJS-25
UL class T
JJS-30
UL class T
JJS-35
UL class T
JJS-40
UL class T
JJS-60
UL class T
JJS-70
UL class T
JJS-70
UL class T
JJS-70
UL class T