3.2.5.4 Connecting Other Optional Components

Table 3-6 Optional component signal cable connection description
Optional
Component
Battery circuit
breaker box (BCB
box)
Ambient
temperature and
humidity sensor
Battery temperature
sensor
iBattery
Dry contact
extended card
Backfeed protection
card
Issue 04 (2019-06-25)
Optional Component Signal Cable
Connected to the Power Unit
Power Unit
Battery Strings
Shared
BCB dry contact on
the dry contact card
(MUE05A) in the
control module of
power unit 1
N/A
COM1 port on the
monitoring interface
card (MUS05A) in
the control module
of power unit 1
Connect the iBattery
of the battery string
to COM2 port on the
monitoring interface
card (MUS05A) in
the control module
of power unit 1.
N/A
N/A
Copyright © Huawei Technologies Co., Ltd.
Power Unit
Battery Strings
Not Shared
Connect the BCB
box of each power
unit battery string to
the BCB dry contact
on the dry contact
card (MUE05A) in
the control module
of the corresponding
power unit.
N/A
Connect the
temperature sensor
of the battery string
of each power unit
to the COM1 port on
the monitoring
interface card
(MUS05A) in the
control module of
the power unit.
Connect the iBattery
of the battery string
of each power unit
to the COM2 port on
the monitoring
interface card
(MUS05A) in the
control module of
the corresponding
power unit.
N/A
N/A
3 Installation
Optional
Component
Signal Cable
Connected to the
Bypass Unit
-
COM1 port on the
monitoring interface
card (MUS05A) in
the control module
of the bypass unit
N/A
N/A
Install in the control
module of the
bypass unit.
Install in the control
module of the
bypass unit.
83