Each time a user operates the keyswitch, the panel changes the current set state. The
keyswitch can full set or unset.
Key Switch Latched – KSL (09)
Use this zone type to connect a fixed position keyswitch to a single zone.
When the user opens the keyswitch contacts, the panel sets the system. When the user
closes the contacts, the panel unsets the system. The keyswitch can full set or unset.
Note:
The keyswitch zone types are intended for use on zones that connect to an access-
control keypad, electronic key or other type of hardwired device used to set or unset
the system.
When the user operates the keyswitch while the system is unset, the panel starts the
programmed exit mode.
When the user operates the keyswitch while the system is set, the panel unsets the
system immediately.
The user cannot reset the system from a keyswitch zone.
Tamper – T (10)
Use this zone type to monitor the tamper status of external equipment. The panel monitors
a Tamper zone at all times. When triggered in the unset condition, only internal sounders
operate. When triggered in the set condition, the alarm response (see page 49) determines
whether the external siren, strobe and communications also respond to the alarm.
HUD Fault – HUD (16)
Use this zone type to monitor the fault output of wired hold-up devices that are capable of
reporting faults. When a detector triggers a zone with this type, the panel generates an
"HUD Fault" alert. If a user tries to set the system when this zone is active, the panel
displays the fault on the keypad. The user can override the fault and carry on setting.
If the alarm system is set, the panel logs the event, starts any programmed communication,
but does not generate an alert until the system is unset.
Once the zone is restored, a user can clear the alert by pressing ✓ and entering their access
code.
Log Only – LO (17)
When a detector triggers a zone with this type, the panel logs the event and activates any
outputs that are programmed to follow this zone. The zone is active whether the system is
set or unset. Typical uses for this zone type are for integrating the alarm system with a
CCTV system.
Note: Zone Follow outputs will activate on both alarm and tamper of a Log Only zone.
Exit Terminate - ET (18)
Use this zone type to terminate setting when the exit mode is Exit Terminate (see page 48).
This zone type is designed for a normally-open momentary switch.
Note that this zone type is armed during the setting time, but inactive both while the
system is set, and while the system is unset. If you apply the Chime attribute to this zone,
the system will give a chime tone when the zone is activated both while the system is unset
and while the system is set.