UPS5000-H-600 kVA-FT(M)
User Manual (FusionPower6000)
Procedure
Step 1 Choose Common Functions > Paral. Inv. OFF on the LCD. The system transfers to
bypass mode.
Step 2 Turn off the general output switch (general load switch) and the external output
power switch, battery switch, external mains input power switch, and then
external bypass input power switch for each UPS.
Step 3 Turn off the internal bypass input switch, output switch, and then mains input
switch of each UPS.
----End
6.4 Performing EPO
Context
Choose Monitoring > UPS System > Running Parameter > System Settings on
the WebUI and set EPO detection to Enable.
● After you press the EPO button, the UPS supplies no power, and the loads
● If the UPS is in maintenance bypass mode, the UPS still supplies power after
Procedure
Step 1 Press the EPO buttons connected to the dry contact cards on all UPSs one by one
or press the general EPO button. All UPSs enter the EPO state.
----End
Issue 02 (2024-01-05)
NO TE
● Perform only step 1 if you only need to shut down the UPS inverters to switch the
system to bypass mode without powering off loads.
● If you need to power off the entire UPS system, perform all the preceding steps.
NO TICE
powers off.
you press the EPO button.
Copyright © Huawei Digital Power Technologies Co., Ltd.
6 Parallel System Commissioning
96