Before performing a shallow discharge test, ensure that:
● If the battery has been replaced, choose System Info > Settings > Battery
● The UPS works in normal mode with a load rate fluctuation less than 10%.
● The UPS does not generate any battery overtemperature, overvoltage, or
● The mains, batteries, charger, and discharger are normal. No overload alarm is
● If the UPS does not communicate with SmartLi 3.0, batteries are managed as
Automatic Shallow Discharge Test
Step 1 On the home screen of the LCD, choose System Info > Settings > Battery
Settings and set Sched. shallow dis. test to Enable.
Step 2 Set Sched. shallow dis. test time and Sched. shallow dis. test interval as
required. After setting is complete, the system will perform an automatic shallow
discharge test based on the settings.
----End
Manual Shallow Discharge Test
Step 1 On the home screen of the LCD, choose System Info > Maintenance > Battery
Maint.
Step 2 Tap Start on the right of Shallow Dis. Test to start a shallow discharge test.
Figure 7-2 Starting a shallow discharge test
Issue 02 (2024-01-05)
NO TICE
Settings on the LCD and verify that the value of Installation time has been
changed based on the actual situation.
overcurrent alarm. No generator is connected to the UPS.
generated.
lead-acid batteries by default. Because the battery capacity is set to the
maximum value on the UPS UI, the battery capacity displayed on the
monitoring UI of the SmartLi should be used during a shallow discharge test.
Otherwise, batteries may be completely discharged.
Copyright © Huawei Digital Power Technologies Co., Ltd.
7 Routine Maintenance
109