UPS5000-H-600 kVA-FT(M)
User Manual (FusionPower6000)
No.
Check Item
5
Ambient
humidity
Product Component Checklist
No.
Check Item
1
Installation
2
Appearance of
the battery
rack or cabinet
3
Battery
appearance
4
Metal scrap
Issue 02 (2024-01-05)
Acceptance Criteria
Actual humidity: ______%
RH (5%–95% RH, non-
condensing)
Acceptance Criteria
The equipment is installed
properly and arranged
neatly, and screws are
tightened.
No dust, rust, or
deformation exists.
● Batteries are clean and
free from stains.
● Battery wiring
terminals are intact.
● Batteries are intact and
free of damage,
deformation, bulges,
and cracks.
● Batteries have no acid
or electrolyte leakage.
(If electrolyte leakage
occurs, there will be a
pungent smell.)
There is no copper scrap
or other conductive
foreign matter.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Check Method and
Troubleshooting
● Check method:
Measure using a
hygrothermograph.
● Troubleshooting: Check
that the air conditioner
runs properly.
Check Method and
Troubleshooting
● Check method: visual
inspection
● Troubleshooting:
Rectify the fault based
on the acceptance
criteria.
● Check method: visual
inspection
● Troubleshooting:
Rectify the fault based
on the acceptance
criteria.
● Check method: visual
inspection
● Troubleshooting:
Contact technical
support.
● Check method: visual
inspection
● Troubleshooting:
Rectify the fault based
on the acceptance
criteria.
7 Routine Maintenance
Check
Interval
Monthly
Check
Interval
Monthly
Monthly
Monthly
Monthly
103