Huawei FusionPower6000 UPS5000-H-600 kVA-FT User Manual page 81

Hide thumbs Also See for FusionPower6000 UPS5000-H-600 kVA-FT:
Table of Contents

Advertisement

UPS5000-H-600 kVA-FT(M)
User Manual (FusionPower6000)
Figure 5-1 Settings Wizard
(1) Lead-acid battery scenario
Step 4 After you set parameters on the Settings Wizard screen, the system displays the
Bypass mode and No battery alarms, which do not need to be handled. Other
alarms need to be handled.
Issue 02 (2024-01-05)
NO TE
● Set the time and date correctly. Incorrect time and date will cause false fault analysis
during maintenance or repair, affecting the normal operation.
● After network parameters are set, connect the UPS to the network, ensuring that
maintenance personnel can manage or control the UPS remotely. If you do not need
remote management, retain the default network parameter settings.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Single UPS Commissioning
(2) Lithium battery scenario
74